Specifications
– | BASIC | PRO |
Dimensions(L*W*H)(mm) | 12192*2438*2896 | 12192*2438*2896 |
Shipping Weight(T) | 13 | 13 |
Operating Weight(T) | 23 | 23 |
Coolant Capacity (L) | 14000 | 14000 |
Cycle Mode | Single loop | Single loop |
Miner Capacity | 384 S19/M50 | 384 S19/M50 |
Tank Quantity | B24 Tank*16 | B24 Tank*16 |
Operating Temperature(℃) | -25°C ~55℃ | -25°C ~55℃ |
Electrical Performance (- /✓ optional/standard)
– | BASIC | PRO |
Input Voltage and Frequency | 3-phase 350-480V 50/60Hz | 3-phase 350-480V 50/60Hz |
Max Power Load (kW) | 1693 | 2822 |
Output Voltage and Frequency | Single-phase 200-277V 50/60Hz | Single-phase 200-277V 50/60Hz |
Safety Certification | CE/UL | CE/UL |
Operating Power(kW) | 100 | 134 |
Power Distribution Cabinets(A) | 1200Ax1 *2 | 1000Ax2 *2 |
PDU | Smart PDU * 16 | Smart PDU * 32 |
Inlet Cable | The inlet cables can withstand high-voltage of above 600V, with the following requirements per phase:L1 4-wires cable 3/0AWG(85mm x4) x1 *2L2 4-wires cable 3/0AWG(85mm x4) x1 *2L3 4-wires cable 3/0AWG(85mm x4) x1 *2N 4-wires cable 3/0AWG(85mm x4) x1 *2PE 1-wire cable 3/0AWG(85mm) x1 *2 | The inlet cables can withstand high-voltage of above 600V, with the following requirements per phase:L1 4-wires cable 3/0AWG(85mm x4) x2 *2L2 4-wires cable 3/0AWG(85mm x4) x2 *2L3 4-wires cable 3/0AWG(85mm x4) x2 *2N 4-wires cable 3/0AWG(85mm x4) x2 *2PE 1-wire cable 3/0AWG(85mm) x2 *2 |
Smart Meter | – | ✓ |
Integrated Wiring | ✓ | ✓ |
Network | ✓ | ✓ |
UPS | – | – |
SPD | ✓ | ✓ |
Cooling Capacity
– | BASIC | PRO |
Cooling Capacity(kW) | 1440 | 1920 |
Cooling Type | Closed water cooling tower or Dry cooler | Closed water cooling tower or Dry cooler |
Inlet Temperature(℃) | 45 | 45 |
Outlet Temperature(℃) | 60 | 60 |
Design Reference Temperature (℃) | 35 | 35 |
Reviews